Wind Energy Data Recording and Monitoring

Overview

Power generator parameters and weather environment data at wind-farms can be recorded. Remote access allows users to monitor all data for operational status.

Application keys

  • Strain gauge sensor at slip-ring and communications across rotating interface.
  • Environmental tolerances (vibration and operational temperatures)
  • Reliable data logging with local storage and ability to feed real-time data to SCADA package
  • Event based recording with reporting options

wind farm app

Benefits

  • Remote monitoring via WAN
  • On site continuous data logging for extended periods
  • Recovery of data logging after power failure
  • Critical diagnostics alarm function
  • E-mail notification by an alarm on math and I/O channels helps users keep track of system for maintenance etc.

Products


pH Measurement in Flue Gas Desulfurization Systems That Use Magnesium Hydroxide Slurry

In flue gas desulfurization systems that use magnesium hydroxide (Mg(OH)2) slurry, the consumption of the desulfurization agent (Mg(OH)2) is controlled by using online pH analyzers. A great concern in the pH measurement is heavy staining of the pH electrodes by the Mg(OH)2 slurry. To ensure accurate measurement, frequent cleaning of the electrodes with an acid is required, adding to both maintenance workload and cost.
The EXA AUTO CLEAN chemical cleaning system automates the acid cleaning process, which not only saves both time and expense but also ensures precise pH measurement over long periods.

pH app Power

Expected Benefits

  • Improves the efficiency of a flue gas desulfurization system with Mg(OH)2 slurry
  • Ensures stable, continuous pH measurement
  • Reduces operating costs
  • Eliminates manual cleaning

Process Overview

In the flue gas desulfurization system, Mg(OH)2 is used as the absorbent to remove sulfur dioxide (SO2) from the flue gas.

Absorption reaction 1: Mg(OH)2 + SO2 ->MgSO3 + H2O
Absorption reaction 2: MgSO3 + SO2 + H2O -> Mg(HSO3)2

After absorbing SO2, the solution undergoes pH adjustment, oxidation, and filtration for detoxification before discharge.

pH adjustment: Mg(HSO3)2 + Mg(OH)2 -> 2MgSO3 + 2H2
Oxidation: MgSO3 + 1/2O2 -> MgSO4

ph App

Field Data
When performing pH measurement in a flue gas desulfurization system with Mg(OH)2 slurry, the electrodes tend to become heavily stained by the slurry. The cleaning of the electrodes and the reduction of maintenance time and cost are key points to consider when selecting a pH analyzer for the system.

field data

Acid cleaning is done with a 4% hydrochloric acid solution

Utilities

Power supply: 100 V AC, 50/60 Hz
Power consumption: approx. 60 VA
Air source: pressure: 300 to 950 kPa
Maximum consumption: approx. 20 L/min
Chemical cleaning solution consumption: approx. 100 mL
Tank effective capacity: approx. 17 L

Notes

  • An organic solvent cannot be used for cleaning.
  • Deterioration of materials in chemical solution piping and air piping
    When the system is installed in a location where it is exposed to direct sunlight, the polyethylene resin piping will last approximately one year. (It is recommended that fluoro resin piping be used.)